Page 22 - Lockwell Industrial Catalogue
P. 22

 MS165 manual motor starters
10 to 65 A – with thermal and electromagnetic protection
MS165-65
MO132-6.3
MO132-32
Rated operational power
400 V AC-31)
kW
0.03 3) 0.06 0.09 0.12 0.25 0.55 0.75 1.5 2.2 4.0 5.5 7.5 7.5 11
15
Rated Short-circuit operational breaking current capacity ICS at
400 V AC
A kA
0.16 100 0.25 100 0.40 100 0.63 100 1.0 100 1.6 100 2.5 100 4.0 100 6.3 100 10 100 12 100 16 100 20 100 25 50 32 25
Rated instanta- neous short-cir- cuit current setting li
A
2.00 2) 3.10 2) 5.00 2) 7.90 2) 12.5 2) 20.0 2) 31.3 2) 50.0 78.8 125 150 200 250 313 400
Type
MO132-0.16 MO132-0.25 MO132-0.4 MO132-0.63 MO132-1.0 MO132-1.6 MO132-2.5 MO132-4.0 MO132-6.3 MO132-10 MO132-12 MO132-16 MO132-20 MO132-25 MO132-32
Order code
1SAM360000R1001 1SAM360000R1002 1SAM360000R1003 1SAM360000R1004 1SAM360000R1005 1SAM360000R1006 1SAM360000R1007 1SAM360000R1008 1SAM360000R1009 1SAM360000R1010 1SAM360000R1012 1SAM360000R1011 1SAM360000R1013 1SAM360000R1014 1SAM360000R1015
Weight (1 pce)
kg
0.215 0.215 0.215 0.215 0.215 0.265 0.265 0.265 0.265 0.265 0.310 0.310 0.310 0.310 0.310
22
Description
MS165 is a compact and powerful range for motor protection up to 30 kW (400 V) / 65 A in width of 55 mm. This type has also a clear and reliable indication of fault in a separate window in the event of short-circuit tripping. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, power in-feed blocks are available as accessory. These are suitable throughout the MS116/MS132/MS165-range.
Ordering details
Rated operational power
400 V AC-3
kW
7.5 7.5 11 15 22 22 30
Setting range
Short-circuit breaking capacity ICS at 400 V AC
Rated instanta- neous short-cir- cuit current setting li
A
240 300 375 480 630 810 975
Type
MS165-16 MS165-20 MS165-25 MS165-32 MS165-42 MS165-54 MS165-65
Order code
1SAM451000R1011 1SAM451000R1012 1SAM451000R1013 1SAM451000R1014 1SAM451000R1015 1SAM451000R1016 1SAM451000R1017
Weight (1 pce)
kg
0.950 0.950 0.960 0.970 0.970 0.970 0.980
AkA
10 ... 16 14 ... 20 18 ... 25 23 ... 32 30 ... 42 40 ... 54 52 ... 65
100 100 100 100 50 30 30
Note: Manual motor starters should always be selected so that the actual motor current is within the setting range.
MO132 manual motor starters magnetic only
0.16 to 32 A – with electromagnetic protection
Description
Manual motor starters magnetic only are electromechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuse-less against short-circuit.
Fuse-less protection with a manual motor starter saves costs, space and ensures a quick reaction under short-circuit condition, by switching off the motor within milliseconds. Fuse-less starter combinations are setup together with contactors and overload relays.
Ordering details
2CDC241008F0011 2CDC241009F0011
2CDC241004V0015
CONTROL
1) For overload protection of motors, an appropriate thermal or electronic overload relay must be used 2) The data is valid for products, produced after week 34, 2014.
3) 690 V








































   20   21   22   23   24