Page 167 - Lockwell Industrial Catalogue
P. 167

                    INTERMEDIATE METERING
PowerLogic remote display.
PowerLogic I/O module.
•
•
– – –
–
– –
– –
–
– – – –
FUNCTIONS AND CHARACTERISTICS
No data gaps due to network outages or server downtime. Min/Max log for standard values.
50 user-definable data logs, recording up to 16 parameters on a cycle-by- cycle or other user definable interval.
Continuous logging or ‘snapshot’ triggered by setpoint and stopped after defined duration.
Trend energy, demand and other measured parameters.
Forecasting via web pages: average, minimum and maximum for the next four hours and next four days.
Time-of-use in conjunction with StruxureWare software.
Event log: alarm conditions, metering configuration changes, and power outages, timestamped to 1 millisecond.
Alarming and control.
50+ definable alarms to log critical event data, trigger waveform recording, or perform control function.
Trigger on any condition, with cycle-by-cycle and 1-second response time. Combine alarms using Boolean logic and to create alarm levels.
Alarm notification via email text message.
In conjunction with StruxureWare Power Monitoring Expert, software alarms and alarm frequency are categorized and trended for easy evaluation of worsening/improving conditions.
Excellent quality: ISO 9001 and ISO 14000 certified manufacturing.
    PowerLogic PM8000 series meter with remote display.
•
–
– –
•
–
–
•
–
– –
–
– –
–
–
– –
Easy installation and setup.
Panel and DIN rail mounting options, remote display option. Pluggable connectors.
Free setup application simplifies meter configuration.
Front panel.
Easy to read colour graphic display.
Simple, intuitive menu navigation with multi-language (8) support.
Flexible remote communications.
Multiple simultaneously operating communication ports and protocols allow interfacing with other automation systems; (e.g. waveforms, alarms, billing data, etc.) can be uploaded for viewing/analysis while other systems access real-time information.
Supports Modbus, ION, DNP3, IEC 61850.
Dual port Ethernet: 10/100base-TX; daisy-chaining capability removes need for additional switches.
Create redundant network loop using Rapid Spanning Tree Protocol (RSTP) and managed Ethernet switches.
Customise TCP/IP port numbers enable/disable individual ports.
RS-485 2-wire connection, up to 115200 baud, Modbus RTU and ION protocols, DNP3 is also supported via RS-485.
Ethernet to serial gateway with Modbus Master functionality, connecting to 31 downstream serial Modbus devices. Also supports Modbus Mastering over TCP/IP (Ethernet) network.
Full function web server with factory and customisable pages to access real- time and PQ compliance data.
Push historical data via email.
Advanced security: Up to 16 configurable user accounts.
Usability